21
MAN0604_Issue 09_02-2013 Apex
2110M8030
Also see drawing 2110C8049 Outline Dimensions of Certied Transmitter, Sensor &
Accessories (available on request from Honeywell Analytics).
General Installation Guidelines
The following general points should be noted before any installation is carried out.
Read all the instructions before starting any of the installation procedures.
Identify a suitable location with a at surface where the Apex Transmitter Unit/
Certied Junction Box can be mounted.
Identify external cable requirements and the necessary cable/conduit entry
ports to be used on the Apex Transmitter Unit/Certied Junction Box.
The Certied Sensor must always point downwards to avoid collection of uids
and other materials on the face.
When tting components that are certied also refer to the Control Drawings
(see Appendix B).
ThesystemcomponentscomplywiththeEMCrequirementsofEN50270.Inordertomaintain
compliance with this standard it is essential that the components are installed correctly as detailed
below. It is the responsibility of the installation design authority to ensure that the electrical
installation meets appropriate standards.
1. The unit should not be electrically connected to electrically noisy (dirty) metalwork or
conductors. The case should be connected to a low noise (clean) earth line via the screen on
theeldcabling.
2. Theentirelengthoftheeldcablingconnectedtoeachunitshouldbefullyscreenedwiththe
screen connected to a low noise earth.
3. The low noise earth line should only be connected to safety earth at a single point. Star
earthing arrangements minimise earth current crosstalk. Field cabling shields should not be
connected such that earth loops are produced.
4. The earth bonding arrangement must ensure that the maximum peak voltage between the
unitcaseearthandanyeldcableconductorislessthan350V.Voltagesinexcessofthiscan
causepermanentdamagetotheunit'sRFIprotectionlters.
5. The use of a single, screening cable for each gas detector ensures maximum screening
and minimum crosstalk. Cabling arrangements which use a single cable for connecting
elddevicescompromisescreening,increasethepotentialforcrosstalkandprevent
implementation of true star earthing.
3. INSTALLATION