EasyManuals Logo
Home>Honeywell>Fire Alarms>Apex

Honeywell Apex User Manual

Honeywell Apex
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #81 background imageLoading...
Page #81 background image
81
MAN0604_Issue 09_02-2013 Apex
2110M8030
4.6.4 Clearing latched alarms
4. OPERATION
The fault and alarm relays may be set to be latched (see CongurationMenu). So when an alarm
message is displayed on the LCD screen it may continue to be displayed even when the fault
causing the problem is corrected.
Note: Alarms may not be set to be latched, but because alarm recovery is set 25% below alarm
setpoint it could appear that they are for a short while.
Toresetalatchedalarmcarryoutthefollowingprocedure:
(1) Press esc at the Gas Reading display.
The Main Menu is displayed.
Main Menu
Calibration Menu
Configuration Menu
Display Menu
History Log Menu
Change Passwords Menu
Reset Passwords
(2) Select (highlight) Display Menu from the list.
(3) Press ok.
(4) When prompted enter the current Level 1 password.
Obtain the password from the system administrator.
The Display Menu is shown.
Display Menu
Reset Alarms, Faults
Calibration Info
Current Config
(5) Select the Reset Alarms, Faults option.
(6) Press ok.
The Reset Alarms, Faults menu is displayed.
WARNING
!
Alarms should not be reset until it is confirmed that
gas is not present.
Reset Alarms, Faults
Reset Alarms
FaultRelay: Inactive
Alarm1 Relay: Inactive
Relay: Inactive
Overrange
:I
nactive
Alarm2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Apex and is the answer not in the manual?

Honeywell Apex Specifications

General IconGeneral
BrandHoneywell
ModelApex
CategoryFire Alarms
LanguageEnglish

Related product manuals