MAN0604_Issue 09_02-2013 Apex
2110M8030
4. OPERATION
4.6.3 4-20mA output signal ranges and fault conditions
22
.
.
20
.
.
6
5
4
3
2
1
0.5
0
mA
Overrange
Warnings
Concentrations
Inhibit
Fault
Pulsed warnings
General Fault Output Signal Level Fault Conditions
Type
Faults 0 - 0.5mA Sensor Failed
(defaultis0.5mA) NoCartridge
Wrong Cartridge
Cartridge Failed
Temperature Error
End of Cell Life
Calibration Needed
No Sensor, Sensor
Comms Fail
Fatal Fault
Warnings 1.0 - 3.5mA
- constant Temperature Error
4.0 - 6.0mA - pulsed 1/sec End of Cell Life
(default is 3mA) Calibration Needed
Over range 20 - 21.5mA Gas Reading exceeded
Warnings (default is 21mA) full scale
Inhibit - Locks relays and outputs