32 LDM Series Instruction Manual — P/N 15885:H3 8/12/2019
System 5000 (UL 8th) MPS-24A Main Power Supply
B.3 MPS-24A Main Power Supply
Connect the power run for the LDMs to MPS-24A TB3, Terminals 1 (+) and 2 (-). Maximum current is 1 amp. The power run to the
LDMs need not contain a Power Supervision Relay since loss of power is inherently supervised.
B.4 MPS-24B Main Power Supply
Connect the power run for the LDMs to MPS-24B, TB2, Terminals 1 (+) and 2 (-). No more than 200 mA current can be drawn from
these terminals in standby or alarm.
P4
P3
TB1
TB2
F1CB1
P5
R27
P2
EARTH GND AC NEUTRAL AC HOT
+24R COMMON +24
COMMON
POWER LIMITED
BAT + BAT -
MPS-24A
Common (-) TB3-2
24 VDC Power (+) TB3-1
Figure B.2 Connecting Power from the MPS-24A
!
CAUTION: POWER-LIMITED WIRING
THE +24 VDC PROVIDED ON TB2 TERMINAL 3 IS POWER-LIMITED ONLY WHEN USED WITH THE MINUS RETURN
ON TB2 TERMINAL 4. DO NOT USE THE MINUS RETURN ON TB2 TERMINAL 2 WITH THE +24 VDC POWER ON TB2
TERMINAL 3.
MPS-24B
24 VDC Power (+) TB2-1
(-) Common TB2-2
Figure B.3 Connecting Power from the MPS-24B

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER LDM Series and is the answer not in the manual?

Honeywell NOTIFIER LDM Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER LDM Series
CategoryControl Unit
LanguageEnglish

Related product manuals