44 LDM Series Instruction Manual — P/N 15885:H3 8/12/2019
Appendix C: NFS2-3030 and NCA-2 (UL 9th), AM2020/AFP1010, NFS-3030, or
NCA (UL 8th)
C.1 Capabilities
When installed with NFS2-3030, NFS-3030, NCA-2, NCA, or AM2020/AFP1010, the LDM Series modules can annunciate the status of
addressable devices, software zones, XP Series Transponder points and several system control functions:
C.2 Devices
Intelligent Detectors
MMX Monitor Modules and CMX Control Modules
BGX Addressable Manual Pull Stations, security devices & all other addressable devices.
Software Zones, logic zones, and digital audio zones
All software zones can be annunciated provided that each zone is mapped to an annunciator point.
System Controls
Acknowledge/Step (referred to as the ACK/STEP key)
Signal Silence
System Reset
Lamp Test (test LEDs, printer & CRT terminal output on FACP/network annunciator only)
XP Series Transponder System
Power and Audio Supply Supervision Point
XPP-1 Form-C Alarm and Trouble Relay Points
XPC Control, XPM Monitor and XPR Relay Module Circuit Points
C.3 Software Versions
All releases of NFS2-3030, NFS-3030, NCA, and ADT-NCA-2 are compatible with LDM series modules.
The AM2020/AFP1010 must be operating with software of the following part numbers (or greater):
AM2020/AFP1010 Board ROM Part Number
Central Processing Unit (CPU-2020) 73123
Display Interface Assembly (DIA-1) 73132
Loop Interface Board (LIB-200) 73117 (for each LIB-200)
C.4 NFS2-3030, NCA-2, and NFS-3030
EIA-485 Connections One EIA-485 circuit may be connected to the CPU-3030/CPU2-3030 or
NCA-2 as shown in the accompanying illustration. The NFS-3030/NFS2-3030/NCA-2 must be at the
end of the EIA-485 circuit. EIA-485 connections are power-limited and supervised; see
Sections 4.3–4.6 for further details and notes about EIA-485 requirements.
Power Connections Connect the power run for the LDMs to TB6 on the AMPS-24/E, CPU2-3030,
NCA-2, or CPU-3030, as shown in the accompanying illustrations. Maximum current for both cir-
cuits on TB6 is 1 amp.
The power run to the annunciator does not require a Power Supervision Relay. Loss of power is
inherently supervised through a Communications loss. This 24 VDC output is supervised, filtered,
and non-resettable. TB6 on AMPS-24/E is power-limited only if the +5V output on the terminal
block is not used; refer to the AMPS-24 Manual for complete details & restrictions if choosing this option.
!
CAUTION:
EACH SOFTWARE ROM INSTALLED IN THE AM2020/AFP1010 MUST BE PART OF THE SAME SOFTWARE
COMBINATION. FOR A LIST OF VALID SOFTWARE COMBINATION NUMBERS, CONTACT THE NOTIFIER
TECHNICAL SERVICES DEPARTMENT.
+
-
3030-acs-TB7.cdr
TB7 on NFS-3030/
NFS2-3030/NCA-2
TB6 on AMPS-24/E
TB6 on CPU2-3030
and NCA-2
TB6 on CPU-3030
amps24-acspower.cdr,
cpu23030-TB6.wmf,

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER LDM Series and is the answer not in the manual?

Honeywell NOTIFIER LDM Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER LDM Series
CategoryControl Unit
LanguageEnglish

Related product manuals