34 LDM Series Instruction Manual — P/N 15885:H3 8/12/2019
System 5000 (UL 8th) AIM-200 Point Annunciation
System 5000 CPU Annunciator Point Assignments to LDMs
System 5000 Option Modules Annunciator Point Assignments to LDMs
Notes:
1. Control Switches marked 'not used' will still function as local LAMP TEST or local ACKNOWLEDGE switches for their
respective points.
2. If Alarm Only Mode is selected, column labeled Yellow LED is not applicable and control switches do not function.
3. If the 8-Point Shift (DIP switch #4 of SW3) is set ON, the eight System 5000 CPU functions (ACK, SIL, RESET, LAMP TEST,
NAC1, NAC2, MUNTIE, RELAY) will be shifted from annunciator points 1 through 8 (as shown above) to points 57 through 64
(provided those points exist in the system and the LDM-32 is set to address 01).
4. Optional control switches are active only if all of these conditions are met:
a) '8-Point Shift' (DIP switch #4) is set to OFF.
b) Receive Only (DIP Switch #5) is set to OFF.
c) Switch Inhibit (DIP Switch #7) is set to OFF.
5. These Status LEDs are active only when the System 5000 is programmed for Output Status.
6. Use green LEDs to indicate activation on controlled output circuits.
7. These control switches require that the System 5000 be programmed for Output Control.
B.6 AIM-200 Point Annunciation
The CPU-5000 can be programmed for an alternate method of annunciating the AIM-200. Up to 192 intelligent devices can be annunci-
ated on a single AIM-200 with LDM series annunciators. The System 5000 annunciates the AIM-200 installed directly to the right of the
CPU-5000. Note that an annunciator cannot be used to execute manual ON/OFF control of intelligent AIM-200 points only standard
System 5000 zones. The option provides annunciation of up to 256 points for the System 5000, broken down as follows:
Annunciator Address 1:
8 CPU points (CPU point shift not an option).
8 unusable points (redundant AIM-200 points).
48 points mapped to the next six modules installed in the
System 5000 (which can also be AIM-200s for annunciation of their 8
software zones.)
System 5000 CPU
Points
LDM Alarm LED Red LDM Trouble/Supv Led Yellow LDM Control Switches
Annunciator Point #1 Indicates System Alarm Indicates System Trouble Functions as an
ACKNOWLEDGE
Annunciator Point #2 not used Indicates that signals have been
silenced
Functions as a SIGNAL
SILENCE
Annunciator Point #3 not used not used Functions as a SYSTEM
RESET
Annunciator Point #4 not used Indicates Supervisory Condition not used
Annunciator Point #5 Indicates that Notification Circuit 1 has
been activated
4
Indicates trouble status of circuit Controls Notification Circuit 1
Annunciator Point #6 Indicates that Notification Circuit 2 has
been activated
4
Indicates trouble status of circuit Control Notification Circuit 2
Annunciator Point #7 Indicates that the Remote Signaling
Municipal Tie has been activated
4
Indicates trouble status of circuit Controls Remote Signaling
Municipal Tie
Annunciator Point #8 Indicates that the Alarm Relay has
been activated
4
Indicates Module Trouble, Power
Failure, or Disabled Circuit(s)
Controls Alarm Relay
Table B.1 System 5000 CPU Annunciator Point Assignments to LDMs
System 5000
Option Modules
LDM Alarm LED Red LDM Trouble/Supv Led Yellow LDM Control Switches
IZM-8 Alarm Status per Circuit Trouble Status per Circuit not used
ICM-4, ICE-4 Indicates Activation
3, 4
Indicates Trouble per Circuit Controls Notification Circuit
5
CRM-4, CRE-4 Indicates Activation
3, 4
Indicates Trouble per Circuit Controls Relays
5
TCM-2, TCM-4 Indicates Activation
3, 4
Indicates Trouble per Circuit Remote Switch Functions
5
AIM-200 Indicates Alarm Status of eight
software zones
Indicates Trouble Status of eight
software zones
not used
Table B.2 System 5000 Option Modules Annunciator Point Assignments to LDMs

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER LDM Series and is the answer not in the manual?

Honeywell NOTIFIER LDM Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER LDM Series
CategoryControl Unit
LanguageEnglish

Related product manuals