LDM Series Instruction Manual — P/N 15885:H3 8/12/2019 35
AIM-200 Point Annunciation System 5000 (UL 8th)
• Annunciator Address 2:
– Intelligent Detectors, addressed 1-64, on the AIM-200 installed next to the CPU-5000.
• Annunciator Address 3:
– Addressable Modules, addressed 1-64, on the AIM-200 installed next to the CPU-5000.
• Annunciator Address 4:
– Intelligent Detectors, addressed 65-96, followed by Addressable Modules, addressed 65-96, on the AIM-200 installed next to the
CPU-5000.
The System 5000 Programming Manual, Document 15584, provides programming instructions for this option. Refer to program choice
'AIM(256).
Alarm and Trouble Mode without 8-Point Shift
Notes:
1) Circuit corresponds to a specific I/O module installed in user configured System 5000.
2) Without 8-Point Shift, the first 8 optional control switches correspond to CPU switch functions: ACK, RES,
NAC 1, NAC 2, MUN TIE, RELAY.
8 CPU
points
8 unusable
AIM-200
points
48 points mapped to the
next six modules installed.
NOTE: AIM-200 detector and module addresses 97, 98 and 99 may be used, but cannot be point-annunciated.
LDM Switch
Position
LDM-32 1st LDM-E32 2nd LDM-E32 3rd LDM-E32
1 ACK Circuit 9 Circuit 25 Circuit 41
2 SIG.SIL. Circuit 10 Circuit 26 Circuit 42
3 RESET Circuit 11 Circuit 27 Circuit 43
4 not used Circuit 12 Circuit 28 Circuit 44
5 NAC 1 Circuit 13 Circuit 29 Circuit 45
6 NAC 2 Circuit 14 Circuit 30 Circuit 46
7 MUN TIE Circuit 15 Circuit 31 Circuit 47
8 Alarm Relay Circuit 16 Circuit 32 Circuit 48
9 Circuit 1 Circuit 17 Circuit 33 Circuit 49
10 Circuit 2 Circuit 18 Circuit 34 Circuit 50
11 Circuit 3 Circuit 19 Circuit 35 Circuit 51
12 Circuit 4 Circuit 20 Circuit 36 Circuit 52
13 Circuit 5 Circuit 21 Circuit 37 Circuit 53
14 Circuit 6 Circuit 22 Circuit 38 Circuit 54
15 Circuit 7 Circuit 23 Circuit 39 Circuit 55
16 Circuit 8 Circuit 24 Circuit 40 Circuit 56
Table B.3 LDM Switch Control Functions