Choosing a location
Choose a location that meets the following criteria:
Table 8 Location criteria
Unpacking the autoloader
Before you begin, clear a work surface to unpack the autoloader. Select an open 2U computer rack
location or choose a desktop location near the host server.
CAUTION: If the temperature in the room where the autoloader will be installed varies by 30
degrees F (15 degrees C) from the room where the autoloader was stored, allow the autoloader to
acclimate to the surrounding environment for at least 12 hours before opening the shipping
container.
Criteria Definition
Standalone requirements Select a location that is flat, sturdy, level, and close to a host
server. Do not place the autoloader on the floor or other
carpeted surfaces.
Do not place the autoloader on its side, upside down, or stack
items on top of the autoloader.
Rack requirements Standard 19-inch rack with 2U of clearance
Room temperature 10-35º C (50-95º F)
Power source
AC power voltage: 100-127 VAC; 200-240 VAC
Line frequency: 50-60 Hz
Locate the AC outlet near the autoloader. The AC power cord is
the product’s main AC disconnect device and must be easily
accessible at all times.
Weight 26 lbs (12 kg)
Air quality
Minimal sources of particulate contamination. Avoid areas near
frequently used doors and walkways, stacks of supplies that
collect dust, printers, and smoke-filled rooms.
Excessive dust and debris can damage tapes and tape drives.
Humidity 20-80% RH non-condensing
Clearance Back Minimum of 15.4 cm (6 inches)
Front Minimum of 30.8 cm (12 inches)
Sides Minimum of 5.08 cm (2 inches)