MD380 User Manual Operation, Display and Application Example
- 57 -
:KHQWKH$&GULYHLVSRZHUHGRQDJDLQDIWHUSRZHUIDLOXUHWKHSDUDPHWHUVWKDWDUHVHOHFWHG
before power failure are displayed.
Select the required parameters by pressing . Set the values of the parameters by
referring to the following example.
1. Determine the parameters to be displayed.
Running frequency. bus voltage, output voltage, output current, output power, output
torque, PID feedback, encoder feedback speed
2. Set the binary data.
F7-03: 0000 0000 0111 1101B, F7-04: 0010 0000 0000 0001B
3. Convert the binary data to hexadecimal data:
F7-03: 007DH, F7-04: 2001H
Set the value on the operation panel: F7-03: H.1043 and F7-04: H.2001.
4.7 Starting or Stopping the AC Drive
4.7.1 Selecting the Start/Stop Command Source
There are three start/stop command sources, namely, operation panel control, terminal
control, and communication control. You can select the command source in F0-02.
Function
Code
Parameter
Name
Setting Range Description Default
F0-02
Command
source
selection
2SHUDWLRQSDQHOFRQWURO
LQGLFDWRU2))
1: Terminal control
LQGLFDWRU21
2: Communication control
(indicator blinking)
Press
RUN
or
STOP
RES
to start
or stop the AC drive.
$',WHUPLQDOQHHGVWREHGH¿QHG
as the run/stop terminal.
7KH0RGEXV578FRPPXQLFDWLRQ
protocol is used.
0
2SHUDWLRQSDQHOFRQWURO
Set F0-02 to 0. After you press
RUN
WKH$&GULYHVWDUWVUXQQLQJWKH581LQGLFDWRU
LV21$IWHU\RXSUHVV
STOP
RES
when the AC drive is in running state, the AC drive stops
UXQQLQJWKH581LQGLFDWRULV2))