6.3. Parallel Battery Alarm Conditions and Connection Test
Setup
Conditions
Symptoms
Diagnosis
Action to Rectify
Notes
HABs
connected in
parallel.
None of the
HABs output
power.
All HAB LCD
screens are lit.
All HAB RUN
LEDs are OFF.
All Alarm LEDs
flash 0.5s on,
0.5s off.
Leader ID
Communication
address fault
protection. No HABs
in the bank have
been set as the
Leader.
Set the address DIP
switch of one HAB to
(1,0,0,0) or (ON, OFF,
OFF, OFF), setting it
as the Leader HAB
HABs
connected in
parallel.
None of the
HABs output
power.
All HAB LCD
Screens are lit.
All HAB RUN
LEDs are OFF.
All Alarm LEDs
flash 0.5s on,
0.5s off.
Leader
Communication ID
Address Repeated.
More than one HAB
has been set as the
Leader.
Set only one HAB
address to 1,0,0,0. All
others should be set
as followers. After
setting the correct
address, restart the
HAB using the front
panel power switch.

Table of Contents

Other manuals for KiloVault HAB 7.5 V3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KiloVault HAB 7.5 V3 and is the answer not in the manual?

KiloVault HAB 7.5 V3 Specifications

General IconGeneral
BrandKiloVault
ModelHAB 7.5 V3
CategoryInverter
LanguageEnglish