BLOWER DATA - DIRECT DRIVE - KGA060
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (larger gas heat section, economizer, wet coil, etc.) See page 41.
2 - Any eld installed accessories air resistance (duct resistance, diffuser, etc.) See page 41.
External Static
Pressure (in. w.g.)
Air Volume (cfm) at Various Blower Speeds
208 VOLTS 230 VOLTS 460/575 VOLTS
High Low High Low High Low
5 Ton Standard Efciency (Downow) KGA060S
0.0 2200 1649 2411 1957 2241 1755
0.1 2256 1669 2417 2002 2221 1742
0.2 2202 1739 2396 1985 2193 1747
0.3 2170 1705 2328 1972 2144 1725
0.4 2158 1689 2293 1959 2104 1695
0.5 2130 1676 2279 1930 2086 1678
0.6 2056 1662 2158 1900 2008 1652
0.7 2032 1657 2089 1857 1975 1610
0.8 1963 1591 2077 1796 1941 1586
0.9 1887 1597 1876 1746 1855 1555
1.0 1695 1400 1746 1601 1778 1486
5 Ton Standard Efciency (Horizontal) KGA060S
0.0 2114 1615 2305 1880 2308 1890
0.1 2115 1610 2290 1876 2334 1906
0.2 2074 1622 2249 1870 2292 1890
0.3 2025 1599 2188 1841 2230 1859
0.4 1996 1577 2148 1812 2210 1846
0.5 1952 1542 2087 1768 2148 1817
0.6 1882 1534 2026 1739 2108 1786
0.7 1838 1488 1966 1680 2094 1743
0.8 1773 1443 1905 1622 1988 1682
0.9 1657 1389 1784 1534 1915 1679
1.0 1548 1335 1672 1462 1853 1506