Page 19
BLOWER DATA - DIRECT DRIVE - KGB060
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (larger gas heat section, economizer, wet coil, etc.) See page 41.
2 - Any eld installed accessories air resistance (duct resistance, diffuser, etc.) See page 41.
External Static
Pressure (in. w.g.)
Air Volume (cfm) at Various Blower Speeds
208 VOLTS 230 VOLTS 460/575 VOLTS
High Low High Low High Low
5 Ton Standard Efciency (Downow) KGB060S
0.0 1940 1581 2131 1788 2131 1788
0.1 1929 1566 2107 1784 2107 1784
0.2 1906 1552 2074 1774 2074 1774
0.3 1872 1546 2036 1752 2036 1752
0.4 1836 1526 1998 1708 1998 1708
0.5 1802 1486 1960 1679 1960 1679
0.6 1749 1447 1904 1635 1904 1635
0.7 1714 1407 1847 1576 1847 1576
0.8 1644 1347 1771 1518 1771 1518
0.9 1574 1245 1658 1430 1658 1430
1.0 1338 - - - 1506 - - - 1506 - - -
5 Ton Standard Efciency (Horizontal) KGB060S
0.0 1930 1575 2143 1764 2143 1764
0.1 1920 1573 2115 1761 2115 1761
0.2 1910 1576 2088 1751 2088 1751
0.3 1870 1552 2055 1746 2055 1746
0.4 1840 1524 2023 1704 2023 1704
0.5 1790 1495 1979 1675 1979 1675
0.6 1739 1466 1925 1633 1925 1633
0.7 1679 1428 1860 1590 1860 1590
0.8 1639 1371 1775 1534 1775 1534
0.9 1559 1270 1670 1421 1670 1421
1.0 1438 - - - 1539 1285 1539 1285