EasyManuals Logo
Home>Lenze>DC Drives>E82EV302K4C

Lenze E82EV302K4C User Manual

Lenze E82EV302K4C
588 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #143 background imageLoading...
Page #143 background image
Basic units in the power range 0.25 ... 2.2 kW
Power connections for 400 V mains voltage
6
Basic unit wiring
6.4
6.4.3
L
6.4-5
EDS82EV903-1.0-11/2002
6.4.3 Power connections for 400 V mains voltage
(
((
( Stop!
l Controller type E82EVxxxK 4 C must only be connected to a
mains voltage of 3/PE AC 320 ... 500 V. Higher mains voltages
will destroy the controller!
l The discharge current to PE is > 3.5 mA. EN 50178 requires a
fixed installation. Double PE connection required.
E82EV551K4B
E82EV751K4B
E82EV152K4B
E82EV222K4B
X1.1
X1.1
L2/N
PE
L1 L2 L3
3/PE AC 400 V
+UG -UG
L1
L3
PE
8200vec011
Fig. 6.4-3 Mains connection 400/500 V 0.55 ... 2.2 kW
X1.1/+UG,
X1.1/-UG
DC supply (DC-bus operation - see Operating Instructions)
Mains connection 400/500 V
8200 vector 0.55 ... 2.2 kW
Show/Hide Bookmarks

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze E82EV302K4C and is the answer not in the manual?

Lenze E82EV302K4C Specifications

General IconGeneral
BrandLenze
ModelE82EV302K4C
CategoryDC Drives
LanguageEnglish

Related product manuals