Basic units in the power range 3 ... 11 kW
Power connections for 400 V mains voltage
6
Basic unit wiring
6.5
6.5.3
L
6.5-5
EDS82EV903-1.0-11/2002
6.5.3 Power connections for 400 V mains voltage
(
((
( Stop!
l Controller type E82EVxxxK 4 C must only be connected to a
mains voltage of 3/PE AC 320 ... 500 V. Higher mains voltages
will destroy the controller!
l The discharge current to PE is > 3.5 mA. EN 50178 requires a
fixed installation. Double PE connection required.
X1.1
3PEAC400V
45 Hz -0 %...65 Hz +0 % 320 V -0 %...550 V +0 %
X1.1
PE L1
L3
+UG -UG
L2
E82EVXXXK4C
L1
L2
L3
N
PE
0,7...0,8 Nm
6.2...7.1 lb-in
6mm/0.24in
8200vec067
Fig. 6.5-3 Mains connection 400/500 V controller 3 ... 11 kW
X1.1/+UG,
X1.1/-UG
DC supply (DC-bus operation - see Operating Instructions)
8200 vector 3 ... 11 kW