Resetting error messages
11
Troubleshooting and fault elimin ation
11.5
L
11.5-1
EDS82EV903-1.0-11/2002
11.5 Resetting error messages
After eliminating the cause for a TRIP error message the error message must be
reset with the ”TRIP reset” order. Only then the drive will start again.
)
))
) Note!
A TRIP error message can have several causes. The TRIP reset
can only be carried out after all causes for the TRIP have been
eliminated.
You can select whether errors occurred are to be reset manually or automatically.
Mains disconnection always carries out a TRIP reset independent of the settings
under C0170.
)
))
) Note!
If the controller carries out more than eight automatic TRIP resets
within ten minutes, the controller will set TRIP rST (Counter
exceeded).
TRIP reset also resets the auto TRIP counter.
Codes for parameter setting
Code Possible settings IMPORTANT
No. Name Lenze Selection
C0043* TRIP reset
-0- No current error
Reset active error with C0043 = 0
v
-1- Active error
C0170
v
Configuration TRIP
reset
0
0 TRIP reset by mains switching, s, LOW–signal
at X3/28, via function module or communication
module
• TRIP reset via function module or
communication mo dule with C0043,
C0410/12 o r C0135 bit 11.
^ 11.5-1
1 like 0 and additional auto TRIP reset
• Auto TRIP reset after the time set under
2 TRIP reset through mains switching, via function
module or communication module
C0171.
3 TRIP reset by mains switching
C0171 Delay for auto-TRIP
reset
0.00 0.00 {0.01 sec} 60.00
Eliminating the cause for TRIP
error message