Basic units in the power range 15 ... 30 kW
Power connections
6
Basic unit wiring
6.6
6.6.2
L
6.6-4
EDS82EV903-1.0-11/2002
6.6.2 Power connections
Mains connection 400/500 V
PE
L1
L2
L3
+UG
-UG
l
0
L1, L2, L3
+UG, -UG
PE
5 Nm
44 lb-in
M6
3/PE AC 400V
1
L1
L2
L3
N
PE
+UG
-UG
Z1
PE
L1
L2
L3
3/PE AC 400V
T2
T1
L2
L3
L1
PE
2
3
3
3
3
4
4
PE L1’ L2’ L3’
Gerät / Load
Z1
PE
L1
L2
L3
+UG
-UG
l
L1, L2, L3
+UG, -UG
PE
5 Nm
44 lb-in
M6
PE
PE
L1
L2
L3
+UG
-UG
l
+UG, -UG
PE
M6
5Nm
44 lb-in
3/PE AC 400V
T1
T2
2,5 Nm
22,1 lb-in
L1 L2 L3
L1, L2,
L3
2-5 Nm
17,7-44,3 lb-in
PE
ϑ>
8200vec288
Fig. 6.6-2 Mains connection 15 ... 30 kW
0
Connection with mains choke
1
Connection with footprint mains filter
2
Connection with built-on mains filter
3
Connection brake chopper ( ^ Operating Instructions for the brake chopper )
4
Connection of temperature monitoring for mains filter (thermal contact)
Z1 Mains choke/mains filter
Fuses and cable cross-sections
8200 vector Mains Inst allation to EN 60204-1 Installation to UL
3)
FI
4)
Fuse L1, L2, L3, PE [mm
2
] Fuse L1, L2, L3, PE [AWG]
E82EV153K4B2x1
1)
M63 A 10 35 A 8
E82EV153K4B2x1
2)
-
... 55
+
M35 A 25 63 A 4
E82EV223K4B2x1
2)
5
z-
...
5
z+
M50 A 16 50 A 6
≥
m
E82EV303K4B2x1
2)
D
450
-0 % ... 775
+0 %
M80 A 25 80 A 3
1)
Without mains choke
2)
With mains choke
Observe national and re gional regulations (e. g. VDE 0113, EN 60204)
3)
Use UL-approved cables, fuses and fuse holders only. UL fuse: 500 ... 600 V, tripping characteristic ”H” or ”K5”
4)
All-current sensitive e.l.c.b.