Basic units in the power range 3 ... 11 kW
Connection of r elay output KSR for ”Safe standstill”
7
Extensions for automation
7.3
7.3.8
L
7.3-17
EDS82EV903-1.0-11/2002
K
3
2
3
3
3
4
X3.1
K
3
1
8200 vector
X3.1
34
+
33
K32 K31
+5V
DC
+24V
=
K
SR
IGBT
8200vec266
Fig. 7.3-10 Relay K
SR
Fig. 7.3-11 Relay connection K
SR
Terminal assignment Dat a
33 Reference potential for the
input safety shutdown
Safety relay Coil voltage at +40°C DC +24 V (+19.5 ... 36
V)
Coil current at 24 V DC 30 mA
Test voltage contact → coil AC 1500 V
eff
for 1 min
34 Input safety shutdown Test voltage contact → contact AC 1500 V
eff
for 1 min
Electrical endurance at rated
load
~10
7
swit ching
operations
Mechanical endurance ~10
7
swit ching
operations
K31
Feedback contact Switching voltage DC 24 V
Feedbac
contact
...
Wiring