Technical Data
821XKlimaBA0399 3-1
3 Technical data
3.1 General data/application conditions
Field Values
Vibration resistance Germanischer Lloyd, general conditions
Humidity class
Humidity class F without condensation(average relative humidity85 %)
Permissible
temperature ranges
during transport of the
controller:
-25
C
¡
+70
C
during storage of the
controller:
-25
C
¡
+55
C
during operation of the
controller:
0
C
¡
+40
C
+40
C
¡
+50
C
without power derating
with power derating
Permissible
installation height h
h
$
1000 m a.m.s.l.
1000 m a.m.s.l.
h
$
4000 m a.m.s.l.
without power derating
with power derating
Degree of pollution VDE 0110 part 2 pollution degree 2
Noise emission Requirements acc. to EN50081-2, EN50082-1, IEC 22G-WG4 (Cv)21
Limit value class A toEN 55011 (industrial area) with mains filter
Limit value class B to EN 55022 (residential area)with mains filter andinstallation into
control cabinet
Noise immunity
Limit values maintained usig mains filter
Requirements according toEN 50082-2, IEC 22G-WG4 (Cv)21
Requirements Standard Severities
ESD EN61000-4-2 3, i.e. 8 kV with air discharge
6 kV with contact discharge
RF interference(enclosure) EN61000-4-3 3, i.e. 10 V/m; 27
¡
1000 MHz
Burst EN61000-4-4 3/4, i.e. 2 kV/5 kHz
Surge
(Surge on mains cable)
EN61000-4-5 3, i.e. 1.2/50
³
s,
1 kV phase-phase,
2 kV phase-PE
Insulation strength Overvoltage categoryIII according toVDE 0110
Packaging (DIN 4180) Dust packaging
Type of protection
Types 821X IP20
NEMA 1: Protection against contact
Types 8215 - 8218 IP 41 on the heat-sink side with thermal separation in
push-through technique
Approvals CE: Low Voltage Directive
Electromagnetic compatibility