Commissioning
5-2 821XKlimaBA0399
5.2 Short set-up (Factory setting)
5.2.1 Switch-on sequence
Step
1.Switch on mains voltage
2.Select the direction of rotation.
-
CWrotation:
- Applya LOWsignal to terminal E4 (0...+3V).
-
CCWrotation:
- Applya HIGHsignal to terminal E4 (+12...+30V).
3.Select the setpoint. Applya voltage 0...+10 V toterminal 8.
4. Enable the controller. Applya HIGHsignal (+12...+30V)toterminal 28.
5.The drive is now operating according to factory setting.
5.2.2 Factory setting of the most important drive
parameters
Setting Code Factory setting Adaption to the
application
Operating mode C001 -0- Setpoint selection via terminal 8
Control via terminals
Parameter setting via 8201BB
Seecodetable,
chapter 7.2
Terminal configuration C007 -0- E4 E3 E2 E1
CW/CCW DC brake JOG1/2/
Seecodetable,
chapter
Machine data Chapter 5.3 ff.
Speed range
Min. field frequency C010 0.00 Hz
Chapter 5.3.1
Max. Field frequency C011 50.00
Hz
Acceleration
and
Acceleration time C012 5.00 s
Chapter 5.3.2
deceleration
times
Deceleration time C013 5.00 s
Current limit
Motor mode C022 150 %
Chapter 5.3.3
values
Generator mode C023 80 %
Drive performance Chapter 5.4 ff.
Current,
Operating mode C014 -4- Motor-current control
Motor-current
power
characteristic
V/f ratedfrequency C015 50.00
Hz
chapter 5.4.2.2
V/f characteristic
V
min
setting C016 0,00 %
-
with constant
Slip compensation C021 0,0 %
min
chapter
5.4.2.1