Technical data
Standards and operang condions
Conformies and approvals
Conformies
CE
2014/30/EU EMC Direcve (reference: CE-typical drive system)
2014/35/EU Low-Voltage Direcve
EAC
TP TC 020/2011
Eurasian conformity: Electromagnec compability of
technical means
TP TR 004/2011 Eurasian conformity: Safety of low voltage equipment
RoHS 2011/65/EU
Restricons on the use of certain hazardous substances
in electrical and electronic devices
Approvals
UL UL 61800-5-1
File No. E132659
for USA and Canada (requirements of the CSA 22.2 No.
274)
Protecon of persons and device protecon
Degree of protecon Data applies to operaonally ready mounted state and
not in wire range of terminals
EN EN 60529 IP20
NEMA NEMA 250 Type 1 protecon against accidental contact only
Insulaon resistance
Overvoltage category EN 61800-5-1
II >2000 m amsl
III 0 … 2000 m amsl
Insulaon of control circuits
EN 61800-5-1 Safe mains isolaon double/reinforced insulaon
Leakage current
AC
EN 61800-5-1
> 3.5 mA
Please observe regulaons and safety instrucons!
DC > 10 mA
Starng current
≤ 3 x rated mains current
Protecve measures
Earth fault resistance Earth-fault protected depending on operang status
Motor stall protecon
Short-circuit strength
Overvoltage resistance
Overtemperature of
motor
I²xt monitoring
EMC data
Operaon on public supply systems The machine or system manufacturer is responsible for
compliance with the requirements for the machine/
system!
> 1 kW, mains current ≤
16 A
EN 61000-3-2
no addional measures
< 1 kW with mains choke
Mains current > 16 A EN 61000-3-12
With mains choke or mains
lter
When designed for rated power.
Noise emission
Category C2
EN 61800-3 see rated data
Category C3
Noise immunity
EN 61800-3 Requirements fullled
Technical data
EMC data
54