EasyManuals Logo
Home>Midea>Air Conditioner>MHC-V4W/D2N8-B

Midea MHC-V4W/D2N8-B Engineering Data

Midea MHC-V4W/D2N8-B
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
M thermal Mono
14 202005
Midea M thermal Mono Engineering Data Book
The circulation pump operation
When zone 1 is ON, P_o(6) starts running; When zone 1 is OFF, P_o(6) stops running;
When zone 2 is ON, SV3(8.1) is ON, P_c(8.2) starts running; When zone 2 is OFF, SV3(8.1) is OFF, P_c(8.2)
stops running .
The floor heating loops require a lower water temperature in heating mode compared to radiators. To achieve
these two set points, a mixing station is used to adapt the water temperature according to requirements of the floor
heating loops. The radiators are directly connected to the unit water circuit and the floor heating loops are after
the mixing station. The mixing station is controlled by the unit.
Midea CAC Confidential

Table of Contents

Other manuals for Midea MHC-V4W/D2N8-B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MHC-V4W/D2N8-B and is the answer not in the manual?

Midea MHC-V4W/D2N8-B Specifications

General IconGeneral
BrandMidea
ModelMHC-V4W/D2N8-B
CategoryAir Conditioner
LanguageEnglish

Related product manuals