Midea M thermal Mono Engineering Data Book
4.2 M thermal Leaving Water Temperature (LWT) Selection
The recommended design LTW ranges for different types of heat emitter are:
For floor heating: 30 to 35⁰C
For fan coil units: 30 to 45⁰C
For low temperature radiators: 40 to 50⁰C
4.3 Optimizing System Design
To get the most comfort with the lowest energy consumption with M thermal, it is important to take account of the following
considerations:
Choose heat emitters that allow the heat pump system to operate at as low a hot water temperature as possible whilst
still providing sufficient heating.
Make sure the correct weather dependency curve is selected to match the installation environment (building structure,
climate) as well as ender users demands.
Connecting room thermostats (field supplied) to the hydronic system helps prevent excessive space heating by stopping
the outdoor unit and circulator pump when the room temperature is above the thermostat set point.
Midea CAC Confidential

Table of Contents

Other manuals for Midea MHC-V4W/D2N8-B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MHC-V4W/D2N8-B and is the answer not in the manual?

Midea MHC-V4W/D2N8-B Specifications

General IconGeneral
BrandMidea
ModelMHC-V4W/D2N8-B
CategoryAir Conditioner
LanguageEnglish

Related product manuals