9
-
'16 • SCM-T-199
1. OUTDOOR UNITS
1.1 Specifications
Model
Item
SCM40ZS-S
Cooling capacity (1) W 4000 (1500 (Min.)
5900 (Max.))
Heating capacity (1) W 4500 (1300 (Min.)
6300 (Max.))
Power source 1 Phase, 220
240V, 50Hz
Operation
data (1)
Power
consumption
Cooling
kW
0.84 (0.59
2.13)
Heating 0.90 (0.54
1.70)
Running
current
Cooling
A
4.2 / 4.0 / 3.8 (220 / 230 / 240V)
Heating 4.4 / 4.2 / 4.0 (220 / 230 / 240V)
Inrush current 4.4 / 4.2 / 4.0 (220 / 230 / 240V)
COP
Cooling 4.76
Heating 5.00
Noise
level
Cooling
Sound level dB (A) 48
Power level dB 62
Heating
Sound level dB (A) 50
Power level dB 64
Exterior dimensions (Height x Width x Depth) mm 595 x780 (+90) x 290
Exterior appearance
(Munsell color)
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 42
Refrigerant
equipment
Compressor type & Q'ty RMT5111MFE2 (Twin rotary type) x 1
Motor (Starting method) kW 1.4 (Line starting)
Refrigerant oil
0.45 (DIAMOND FREEZE MA68)
Refrigerant (4) kg R410A 1.9 (Pre-Charged up to the piping length of 30m)
Heat exchanger M fins & inner grooved tubing
Refrigerant control Capillary tubes + Electronic expansion valve
Device control Microcomputer control
Air handling
equipment
Fan type & Q'ty Propeller fan x 1
Motor W 24
Air flow
Cooling
m
3
/min
32.5
Heating 32.5
Shock & vibration absorber Cushion rubber (for compressor)
Electric heater Crank case heater (220V 20W)
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Outdoor fan motor error protection,
Heating & Cooling overload protection
Installation
data
Refrigerant piping size (O.D) mm
Liquid line:
φ
6.35 (1/4") × 2
Gas line:
φ
9.52 (3/8") × 2
Connecting method Flare connecting
Insulation for piping Necessary (Both sides), independent
Length for one indoor unit
m
Max. 25
Total length for all rooms Max. 30
Vertical height difference between
outdoor unit and indoor unit
Max. 15 (Outdoor unit is higher)
Max. 15 (Outdoor unit is lower)
Height difference of the indoor units Max. 25
Recommended breaker size A 25
Connection wiring
Size x Core number 1.5mm
2
x 4 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
IP number IPX4
Accessories (included) Installation sheet, Elbow, Grommet
Indoor unit to be combined
SRK20,25,35ZMX-S
SRK20,25,35ZS-S
SKM20,25,35ZSP-S
SRF25,35ZMX-S
SRR25,35ZM-S
FDTC25,35VF
Number of connectable indoor units 2
Total of indoor units kW Max. 6
Notes (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO-T1, JIS C 9612
Heating 20˚C 7˚C 6˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) The operation data are applied to the 220/230/240V districts respectively.
(4) The refrigerant quantity to be charged includes the refrigerant in 30m connecting piping.
(Purging is not required even for the short piping.)
The pipe length for one indoor unit is 5m.
Adapted to
RoHS
directive
A
RWC000Z291

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SCM45ZS-S and is the answer not in the manual?

Mitsubishi SCM45ZS-S Specifications

General IconGeneral
BrandMitsubishi
ModelSCM45ZS-S
CategoryAir Conditioner
LanguageEnglish

Related product manuals