33
-
'16 • SCM-T-199
Model
Item
SRF25ZMX-S
Power source 1 Phase, 220
−
240V, 50Hz
Operation data
Nominal cooling capacity (range)
kW 2.5
Nominal heating capacity (range)
kW 3.4
Sound power level
Cooling
dB(A)
51
Heating 51
Sound pressure level
Cooling Hi: 40 Me: 32 Lo: 29 ULo: 26
Heating Hi: 40 Me: 35 Lo: 33 ULo: 28
Silent mode sound pressure level
—
Exterior dimensions (Height x Width x Depth) mm 600 x 860 x 238
Exterior appearance
( Munsell color )
Fine snow
( 8.0Y 9.3/0.1 ) near equivalent
Net weight kg 18
Heat exchanger Louver fins & inner grooved tubing
Fan type & Q'ty Turbo fan x 1
Fan motor (Starting method) W 40 x1 (Direct drive)
Air flow
Cooling
m
3
/min
Hi: 9.0 Me: 7.6 Lo: 6.7 ULo: 5.8
Heating Hi: 10.5 Me: 8.2 Lo: 7.7 ULo: 6.6
Available external static pressure Pa 0
Outside air intake Not possible
Air filter, Quality / Quantity Polypropylene net ( washable ) x 1
Shock & vibration absorber Rubber sleeve (for fan motor)
Operation control
Remote control Wireless remote control
Room temperature control Microcomputer thermostat
Operation display
RUN: Green, TIMER: Yellow, HI POWER: Green, Air outlet selection: Green, ECONO: Green
Safety equipments Frost protection, Serial signal error protection, Indoor fan motor error protection
Installation data
Refrigerant piping size ( O.D ) mm Liquid line:
φ
6.35 ( 1/4" ) Gas line:
φ
9.52 ( 3/8" )
Connecting method Flare connection
Attached length of piping m —
Insulation for piping Necessary (Both sides), independent
Drain hose Hose connectable ( VP16 )
Drain pump, max lift height mm —
Interconnecting wires Size x Core number 1.5mm
2
x 4 cores ( Including earth cable ) / Terminal block ( Screw fixing type )
IP number IPX0
Standard accessories
Mounting kit, Clean filter ( Allergen clear filter x 1, Photocatalytic washable deodorizing filter x 1 )
Option parts Interface kit ( SC-BIKN-E )
Notes (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO5151-T1
Heating 20˚C — 7˚C 6˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher
due to ambient conditions.
The pipe length is 7.5m.
Adapted to
RoHS
directive
(2) Floor standing type (SRF)
A
RWB000Z056