273
-
'16 • SCM-T-199
Error code
Remote control:
LED Green Red
Content
Indoor
Keeps flashing
Stays OFF
E58
Current safe stop
Outdoor
3
-
time ash
Error code
Remote controller: E58
LED Green Red
Indoor
Outdoor
Content
Current safe stop
(Model SRC40 - 60)
Keeps flashing
Stays Off
3 time flash
1. Applicable model
5. Troubleshooting
All models
When the current safe control
has operated at the compressor
speed of 30 rps or under:
Same as above
• Excessive refrigerant amount
• Indoor,outdoor unit installation
spaces
• Faulty compressor
• Defective outdor air temp.
sensor
• Defective outdoor main PCB
Diagnosis Countermeasure
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
Note:
Is outdoor
ventilation condition
good ?
Inspect
outdor air temp.
sensor
Is the refrigerant
amount nomal ?
Adjust the refrigerant
amount properly.
Secure space for inlet and
outlet.
Replace compressor.
Replace sensor.
Defective outdoor main
PCBReplace.
(Defective outdor air temp.
sensor input circuit)
Inspect
compressor
YES
YES
YES
NO
NO
NO
NO
YES

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SCM45ZS-S and is the answer not in the manual?

Mitsubishi SCM45ZS-S Specifications

General IconGeneral
BrandMitsubishi
ModelSCM45ZS-S
CategoryAir Conditioner
LanguageEnglish

Related product manuals