EasyManuals Logo
Home>Mitsubishi>Air Conditioner>SCM45ZS-S

Mitsubishi SCM45ZS-S User Manual

Mitsubishi SCM45ZS-S
335 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #240 background imageLoading...
Page #240 background image
-
239
-
'16 • SCM-T-199
None
Louver motor failure
(FDTC and FDE series)
Keeps ashing
Stays OFF
Outdoor
Stays OFF
1. Applicable model
5. Troubleshooting
FDTC and FDE series only
Diagnosis Countermeasure
NO
YES
Is LM wiring
broken?
Is LM locked?
Check at the indoor unit side.
LM: louver motor
Is the louver
operable with the remote
control?
YES
NO
Does the louver
operate at the power
on?
YES
NO
YES
NO
Operate after
waiting for more
than 1 minute.
Repair wiring.
Defective indoor control
PCB
Replace.
Replace LM.
Normal
Adjust LM lever and then
check again.
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
Defective LM
LM wire breakage
Faulty indoor control PCB
Note:
Error code
Remote control:
LED Green Red
Indoor
Content