14
Fan
UserSuperuser
Standby - Ventilation at pause
It can be a good idea to set the ventilation at pause when you on a summer day, for instance, have all the windows and
doors open. In this period, hot water will be produced via the electrical supplementary.
Pause ventilation is set in the Standby menu:
• CP/Pause ventilation Here the ventilation is set at pause.
Off: Ventilation ON
On: Ventilation is shut down until next change in the weekly schedule.
(The ventilation starts automatically at the next change in the weekly plan if the
weekly schedule is created.)
Standby - System state
It is possible to read how the ventilation is running.
System state is read in the Information menu:
• CP/System state Display system operating mode.
Auto: System operation - normal settings
User: System operation - special settings
Inact: System is shut down
Standby - Operating modes
You can change system settings to run the system in different operating modes.
Operating modes are set in the Standby menu:
• CP/Automatic – ON The system is running according to the pre-defined settings.
• CP/Heating Manual Operate – ON: The system is running (heating only)
• CP/Cooling Manual Operate – ON: The system is running (cooling only)
NB! Only one of the above options may be active.