AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 36
Power Supply Calculations Electrical Specifications
A.6.3 Calculation for Main Supply Current
Quantities
Calculation Column 1
Primary, Quiescent
Current (amps)
Calculation Column 2
Primary, Fire Alarm
Current (amps)
AFP-3030/NCA-2 with display
AFP-3030/NCA-2 without display
[ ]
[ ]
x [0.205]=
x [0.140]=
x [0.225]=
x [0.150]=
LCM-320 (refer to Doc. 51330,52544)
LEM-320 (refer to Doc. 51330,52544)
[ ]
[ ]
x [0.130]=
x [0.100]=
x [0.130]=
x [0.100]=
SLC Loop
*
* Value represents an SLC’s maximum current draw. Refer to device datasheets for individual current
draws. Total device current cannot exceed 200 mA.
[ ]
x [0.200]= x [0.200]=
NCM-W, NCM-F
HS-NCM-W/MF/MFSF/WMF/WSF
[ ]
[ ]
x [0.110]=
x [0.400]=
x [0.110]=
x [0.400]=
DVC components (Refer to DVC manual)
[ ]
[ ]
x [ ]=
x [ ]=
x [ ]=
x [ ]=
DVC-RPU components (Refer to DVC-RPU
manual)
[ ]
x [ ]= x [ ]=
DA-30/DA-60/DA-120 (Refer to DOC-01-
004)
[ ] x [ ]= x [ ]=
FSD-751RPL (Duct Detector) [ ] x [0.025]= x [0.087]=
FSA-8000/FSA-20000 (FAAST Detector) [ ] x [0.465]= x [0.493]=
ACM-24AT
ACM-48A
AEM-24AT
AEM-48A
[ ]
[ ]
[ ]
[ ]
x [0.016]=
x [0.016]=
x [0.002]=
x [0.002]=
x [0.070]=
x [0.070]=
x [0.056]=
x [0.056]=
Maximum number of LEDs illuminated on
these annunciators during quiescent
conditions:
[ ] x [0.0054]=
SCS-8A (refer to Doc. 15712) [ ] x [ ]= x [ ]=
LCD2-80
ACM-8RA
LDM (refer to Doc. 15885)
ACM-ZM
AEM-ZM8
ARM (Refer to DOC-01-005)
ARE Interface
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.100]=
x [ 0.020]=
x [ ]=
x [0.020]=
x [0.005]=
x [ ]=
x [0.020]=
x [0.100]=
x [0.035]=
x [ ]=
x [0.025]=
x [0.025]=
x [ ]=
x [0.035]=
FZM-1, MMX-2 [ ]
x [0.0094]= x [0.090]=
Four-Wire Smoke Detectors
[ ]
[ ]
x [ ]=
x [ ]=
x [ ]=
x [ ]=
Compatible Devices not listed above
†
† Refer to manual and/or Device Compatibility Document.
[ ]
[ ]
x [ ]=
x [ ]=
x [ ]=
x [ ]=
Sub-totals Primary,
Quiescent:
Primary,
alarm:
Battery [ ]
x [AH
‡
] x [0.1]=
‡ Value represents battery size in amp hours. Refer to Appendix A.7, “Calculating the Battery Requirements”, on page 38
to determine battery size.
Sum each column for totals Primary,
Quiescent:
Primary,
alarm:
Table A.2 System Draw Current Calculations