AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 4
Specifications System Overview
2.2 Specifications
2.2.1 Supply Rating
2.2.2 Environmental Specifications
2.3 System Components
Central Processing Unit (CPU) with Power Supply. The central processing unit for the
AFP-3030 is a combination of the CPU and on board power supply (NPS-5CHS or NPS-11CHS).
The power supply provides +24 V DC power and a battery charger for the basic system. Auxiliary
power supplies and/or battery chargers are available to customize large systems.
Indicating Unit. The indicating unit acts as the primary display for the status of the Fire System.
The ACM-ZM provides the status indications, with the AEM-ZM providing additional zonal indi-
cations. The Indicating Unit also provides a Bulgin Switch for Trial Evacuation, a Bulgin Switch
for Silence, and a Door Switch.
Keypad/Display. The keypad with built in LCD display serves as a secondary display for the
AFP-3030.
Enclosures. Five cabinet sizes are available; CAB650, CAB900, 18U, 28U, and 40U. Refer to
Section 2.5, “System Cabinets”, on page 8 for additional information.
SLC Loops: LCM-320, LEM-320 . To provide one SLC loop, connect one LCM-320 to the
panel. Connect an LEM-320 to the LCM-320 to provide a second loop. Up to five pairs of modules
can be installed on the panel to provide a maximum of ten SLC loops.
Network Connection. Connect a wire or fibre version of the NCM or the HS-NCM to provide a
connection to the Noti•Fire•Net (network version 5.0 or higher) or High-Speed Noti•Fire•Net.
Annunciators. The AFP-3030 supports ACM-24AT/ACM-48A (and their expanders) with either
64 or 96 points at an address, as well as LDM-32 (and expanders) and Notifier’s other ACS
devices. (See Section 2.6 “Compatible Equipment” if looking for specific ACS devices.)
Supply Rating Parameter Details
Input Fuse Rating M205 Fuse - 250V, 8.0A
Input Voltage Rating NPS-5CHS: 100-240 V AC, 50-60 Hz, 0.8-2.5 A
NPS-11CHS: 100-240 V AC, 50-60 Hz, 1.5-5.0 A
Output Ratings Details
Output Current NPS-5CHS: 5.6 A
*
@ 27.3 V DC
NPS-11CHS: 11.7 A
*
@ 27.3 V DC
*A total of 15 A can be drawn from the panel, with the difference in current being
drawn from the panel batteries.
Output Ratings (Charger) Details
Charger Voltage 27.3 V DC
Environmental Specifications
Parameters
Details
Environmental Limits 0°C to 49°C dry heat
40°C @ 93% relative humidity
IP Rating CAB650, CAB900: IP30
18U, 28U, 40U: IP52
NOTE: Annunciators for the AFP-2800 operate on a different baud rate and are not compatible