ID50 Series Panel - Operating Manual
Operator Actions at Panel
41 997-264-000-8, Issue 8
January 2007
4.12.4 Input Events - User Option
The Input Events menu option allows the user to view
active input events/plant alarms while the normal active
input events/plant alarms display has been overridden
by a higher priority display (alarms). To view Plant Alarms,
from the VIEW Mode menu:
1 Using the numeric keypad, press the ‘
4
’ button to
select the Input Events display.
2 The LCD automatically displays either:
a. The first input event, or
b. The ‘No Warnings message’, if there are no current
input events recorded on the system.
3 If a number of input events are present, press the
‘
2
/
8
’ buttons to scroll through the entries:
a. Plant Alarm condition
b. Alarm currently displayed.
c. Number of alarms.
d. Zone Number.
e. Device Address.
f. Device Type.
g. Time alarm was logged.
h. Zonal and Device text
(if any).
Note: Plant alarms for Hold Switch and Abort Switch
inputs are entered as AUX events in the Fault list.
These input events are not processed by any CBE
rules.
4 Press the ‘
4
’ button to return to the View Mode
menu.
[U0 View] 1:Log 2:Devices 3:Faults
4:Input Events 5:Disabled ↕ : More
PLANT 01 / 10 Z21 M12 AUX 14:55
< - - - Zone Text - - - > < - - - Device Text - - - >
The system has NO warnings present
<:Exit
PLANT 01 / 10 Z21 M12 AUX 14:55
< - - - Zone Text - - - > < - - - Device Text - - - >
ABCDEFG
H
PLANT 02 / 10 Z17 M05 MON 15:05
< - - - Zone Text - - - > < - - - Device Text - - - >
2
8
4