ID50 Series Panel - Operating Manual
Operator Actions at Panel
44997-264-000-8, Issue 8
January 2007
4.12.8 Version - User Option
The Version User Option allows the user to view the System
and Loop part numbers and revision levels used in the
system. To view the Versions, from the View Mode menu:
1 Using the numeric keypad, press the ‘
8
button to
select the Versions display.
* ID60 panel only
2 The LCD automatically displays the following. Press
the ‘
4
button to cancel and return to the View Mode
menu.
4.13 Commissioning
The Commissioning User Option is available to Level 3
users only (i.e. the Level 3 access code must be entered).
The Commissioning menu allows the engineer to
configure the system in preparation for handover.
For details concerning commissioning and configuring
the system, refer to 997-263, ID50 Series Panel -
Installation, Commissioning & Configuration Manual,
Sections 4 and 5.
4.14 Print
The RS232 Protocol option has to be set to ‘Printer’ for
this option to become available. If available, the panel’s
event log and disablements can be printed using an
external printer or displayed on a terminal or saved as a
file on a PC connected to the RS232 port.
To print the event log:
1 From the top level menu, press the ‘
6
’ button to select
the Print option. The following options are displayed:
1
ID60 option only.
2 Press the ‘
1
’ pushbutton to select the Print Log
option.
Part Number
Revision Level
[U0 VERSION] System : nnn-nnn-nnn n.nn
Loop : nnn-nnn n.nn
8
[U0] 1 : Test 2 : Disable/Enable 3 : Clock
4 : View Mode 5 : Commission 6: Print
[U0 PRINT] 1 : Log 2 : Disablements
3 : Maintenance
1
[U0 PRINT LOG] 1 : All 2 : Fire 3 : Fault
4 : Pre-Alarm 5 : Test 6: Disablement
6
1
[U0 View] 6: Maint.* 7: Alarm Count
8: Voltages 9: Version : More