Wiring Section 5-3
R ≤ (R
IN
× V
OFF
)/(I
leak
× R
IN
– V
OFF
)
Power W
≥ (V
CC
– V
R
)
2
/R × 4 [allowable margin]
4. Precautions on Sensor Surge Current
An incorrect input may occur if a sensor is turned ON after the PLC has
started up to the point where inputs are possible. Determine the time re-
quired for sensor operation to stabilize after the sensor is turned ON and
take appropriate measures, such as inserting into the program a timer de-
lay after turning ON the sensor.
Example
In this example, the sensor’s power supply voltage is used as the input to
CIO 000000 and a 100-ms timer delay (the time required for an OMRON
Proximity Sensor to stabilize) is created in the program. After the Comple-
tion Flag for the timer turns ON, the sensor input on CIO 000001 will cause
output bit CIO 000100 to turn ON.
Output Wiring Precautions
Output Short-circuit
Protection
If a load connected to the output terminals is short-circuited, output compo-
nents and the and printed circuit boards may be damaged. To guard against
this, incorporate a fuse in the external circuit. Use a fuse with a capacity of
about twice the rated output.
Transistor Output
Residual Voltage
A TTL circuit cannot be connected directly to a transistor output because of
the transistor’s residual voltage. It is necessary to connect a pull-up resistor
and a CMOS IC between the two.
Output Surge Current When connecting a transistor or triac output to an output device having a high
surge current (such as an incandescent lamp), steps must be taken to avoid
damage to the transistor or triac. Use either of the following methods to
reduce the surge current.
V
R
R
V
CC
R
IN
V
CC
:
V
ON
:
V
OFF
:
I
ON
:
I
OFF
:
R
IN
:
V
R
:
I
OUT
:
I
leak
:
R:
Sensor output residual current
Sensor control current (load current)
Sensor leakage current
Bleeder resistance
Power voltage
PLC ON voltage
PLC OFF voltage
PLC ON current
PLC OFF current
PLC input impedance
Two-wire sensor
DC Input Unit
TIM
0000
#0001
000000
000100
TIM0000 000001

Table of Contents

Other manuals for Omron CJ1M-CPU series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ1M-CPU series and is the answer not in the manual?

Omron CJ1M-CPU series Specifications

General IconGeneral
BrandOmron
ModelCJ1M-CPU series
CategoryController
LanguageEnglish

Related product manuals