7-45
7 High-speed Counters
CJ2M CPU Unit Pulse I/O Module User’s Manual
7-5 Application Examples
7
2 Select an input frequency of 100 kHz max. for the counter setting for high-speed counter 0.
3 Select Linear mode for the counting mode.
4 Select Software Reset for the reset method.
5 Select Continue for the comparison operation after resetting.
6 Select Differential Phase for the pulse input mode.
7 Transfer the PLC Setup to the CJ2M CPU Unit.
8 Close the PLC Settings Dialog Box.
9 Turn the power supply to the PLC OFF and then back ON.
The changes made to the PLC Setup will be applied.