4-3SectionProgramming Example
120
4-3 Programming Example
This section demonstrates all of the steps needed to write a program with the
Programming Console.
4-3-1 Preparatory Operations
Use the following procedure when writing a program to the CPM2A for the first
time.
1, 2, 3... 1. Set the Programming Console’s mode switch to PROGRAM mode and turn
on the CPM2A’s power supply. The password input display will appear on
the Programming Console.
RUN
MONITOR
PROGRAM
<PROGRAM>
PASSWORD!
2. Enter the password by pressing the CLR and then the MONTR Key.
CLR MONTR
<PROGRAM> BZ
3. Clear the CPM2A’s memory by pressing the CLR, SET, NOT, RESET, and
then the MONTR Key. Press the CLR Key several times if memory errors are
displayed.
CLR
00000
SET
NOT
RESET
00000MEMORY CLR?
HR CNT DM
MONTR
END HR CNT DM
00000MEMORY CLR
4. Display and clear error messages by pressing the CLR, FUN, and then the
MONTR Key. Continue pressing the MONTR Key until all error messages
have been cleared.
CLR
00000
FUN
00000
FUN (0??)
MONTR
ERR/MSG CHK OK
5. Press the CLR Key to bring up the initial programming display (program ad-
dress 00000). The new program can be written at this point.
CLR
00000
Caution Check the system thoroughly before starting or stopping the CPM2A to prevent
any accidents that might occur when the program is first started.