5-6SectionMaintenance Inspections
141
5-6 Maintenance Inspections
In order for your SYSMAC system to operate in optimum condition, be sure to
carry out daily or periodical inspections.
Inspection Items The main system components of a SYSMAC system are semiconductors, and it
contains few components with limited lifetimes. Poor environmental conditions,
however, can lead to deterioration of the electrical components, making regular
maintenance necessary.
The standard period for maintenance checks is 6 months to 1 year, but more fre-
quent checks are required if the PC is operated in more demanding conditions.
If the criteria are not met, adjust to within the specified ranges.
Inspection items Details Criteria Remarks
Power supply Determine whether the voltage fluctuation
at the power supply terminals is within
specifications.
Within the voltage variation
range (see note)
Tester
Environmental
conditions
Is the ambient temperature inside the
panel appropriate?
0 to 55_C
Thermometer
Is the ambient humidity inside the panel
appropriate?
10% to 85% RH with no
condensation
Hygrometer
Has dirt or dust collected? None Visual inspection
I/O power supply Is the voltage fluctuation measured at the
I/O terminals within the standard range?
Each I/O terminal must
conform to the specifications
Tester
Installation status
Are all units securely installed? Nothing is loose Phillips screwdriver
Are all connection cables and connectors
inserted completely and locked?
Nothing is loose Visual inspection
Are any of the external wiring screws
loose?
Nothing is loose Phillips screwdriver
Are any of the external wiring cables
frayed?
No external abnormalities Visual inspection
Product service life
Contact output relay Electrical:
Resistance load:
300,000 operations
Inductive load:
100,000 operations
Mechanical:
10,000,000 operations
---
Battery (CPM2A-BAT01) 5 years* ---
Note Power supply voltage variation range.
Power supply Allowable voltage fluctuation range
100 to 240 VAC 85 to 264 VAC
24 VDC 20.4 to 26.4 VDC
Standard Tools (Required)
• Screwdrivers (Phillips and flat-blade)
• Voltage tester or digital voltage meter
• Industrial alcohol and a cotton cloth
Measurement Devices (May be Needed)
• Synchroscope
• Cathode-ray oscilloscope
• Thermometer, hygrometer
Note Do not attempt to disassemble, repair, or modify the PC in any way.
* Data will continue to be backed up for one week after a battery error occurs.
Required Tools