6 Programless Communications
6 - 16
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
(5) copy and execute the copy operation.
If you select all, the parameters settings will be copied to all of the slaves. If you select a
number, the parameters settings will be copied to the slave with the selected
communications unit number.
Note: 1 You cannot cancel copying once the copying operation has been started. Even if you change the set value
during the copying operation, the current processing will be continued.
2 If copying fails, the copying operation will be aborted and the parameter settings will not be copied to the
remaining slaves.
3 The following parameters are not copied.
Auto/Manual
RUN/RESET
SP Mode
Hold
Manual MV
For a Mitsubishi PLC, the ERR. indicator on the Serial Communications Module will light during the
copying process, but this does not indicate an error. The ERR. indicator will go out when the PLC is
restarted.
Refer to 6-4-4 E5
@
C-T Controller Setup for specific copying procedures.
Set value Description
off
(e0**)
Copying is not in progress. The display will automatically return to off when the
copy operation is completed normally.
If the copy operation fails,E** will be displayed instead of
off. The asterisks will
be replaced with the communications unit number of the slave where copying
failed.
Example: If copying failed at the slave with communications unit number 2,
e002
will be displayed.
all The parameter settings are copied to the slaves starting with the slave with
communications unit number 1 and continuing on to the slave with the
communications unit number that is set in the Highest Communications Unit No.
parameter. When copying is started, the PV display on the slave will change to
copy. The copying operation is completed when all of the slaves are reset.
1 to 31 The parameter settings are copied to the slave with the specified communications
unit number, and then all of the slaves are automatically reset.

Table of Contents

Other manuals for Omron E5*C Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5*C Series and is the answer not in the manual?

Omron E5*C Series Specifications

General IconGeneral
BrandOmron
ModelE5*C Series
CategoryController
LanguageEnglish

Related product manuals