2 - 9
2 CompoWay/F Communications Procedures
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
2-3 Detailed Description of the Services
2
2-3-2 Write Variable Area
• Error Occurred
(5) Precautions
• Alarm Function
Even though alarms are not displayed on the Controller's display, they function normally in
communications.
This service writes data to the variable area.
• Service Request PD
• Service Response PDU
(1) Variable Type and Write Start Address
For details on variable types and write start addresses, refer to Section 3 Communications Data for
CompoWay/F.
(2) Bit Position
Bit access is not supported. Fixed to “00.”
(3) Number of Elements
Response code Error name Cause
1001 Command too long The command is too long.
1002 Command too short The command is too short.
1101 Area type error The variable type is wrong.
1103
Start address out-of-range error The read start address is out of
range.
110B
Response too long The number of elements exceeds
the maximum.
1100 Parameter error Bit position is not “00.”
2203 Operation error Non-volatile memory error
2-3-2 Write Variable Area
Number of elements Processing
0000
The write operation is not performed (do not append write
data to the service request PDU) and processing ends in a
normal completion.
Double word
(variable types C1, C3, C4, C5,
C9, or DA)
0001 to 0018
(1 to 24)
The write operation is performed and processing ends in a
normal completion.
Word
(variable types 81, 83, 84, 85, 89,
or 9A)
0001 to 0030
(1 to 48)
MRC SRC
0102 00
222244
Variable
type
Start write
address
Bit
position
Number of
elements
Write Data (for number
of elements)
Number of elements
× 8 or 4
MRC SRC
0102
22 4
Response
code