6 Programless Communications
6 - 28
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
(4) Select Options
Transfer to PLC from the menu bar in the window that is shown
above. The settings will be transferred.
Close the window and cycle the power to the PLC. This completes the PLC setup pro-
cedure. You will use the CX-Programmer to check operation, so leave it online.
This section describes the setup for programless communications. Refer to 6-2 E5
@
C-T Controller
Setup for the procedure to display parameters. Here we will assume that all parameters other than
those for communications have already been set. Make sure that all of the E5@C-T Controllers are the
same model. The parameter settings cannot be copied if the models are different.
(1) Set the Communications Unit No. parameter (u-no) in the communications setting
level to 1 for the No. 1 Controller (E5CC-T) and set it to 2 for the No. 2 Controller.
The default communications unit number is 1, so the Communications Unit No. parameter
for the No. 1 Controller does not need to be changed.
Always set the communications unit numbers of the slaves in order from 1.
To enable the changes to the settings, always return to the operation level.
(2) Change the parameter settings in the communications setting level of the No. 0
Controller to the values that are given below.
Protocol Setting (psel): fins (Set mcp4 for a Mitsubishi PLC.)
Communications Unit No. (u-no): 0
Communications Baud Rate (bps): 57.6
Send Data Wait Time (sdwt): 1
Highest Communications Unit No. (maxu): 2
Do not return to the operation level even after you finish making the settings.
Here we will assume that all parameters other than those for communications have already
been set. If parameters other than those for communications need to be set, change them
first and then change the communications settings last.
(3) Perform the following procedure to copy the parameter settings in the No. 0
Controller to the No. 1 and No. 2 Controllers.
(a) Display the copy parameter in the communications setting level on the No. 0
Controller.
(b) Press the Up Key to select all and wait for three seconds. The completion of the
copy operation must be confirmed, so do not move to any other levels or param-
eters. If you do change to any other levels or parameters, display the copy
parameter again.
(c) The PV displays on the No. 1 and No. 2 Controllers will change to copy and then
these Controllers will be reset.
(d) Confirm that the setting of the copy parameter on the No. 0 Controller changes
to off (i.e., copying completed), and then return the No. 0 Controller to the
operation level.
(e) Programless communications should now be operating. Confirm that the COMM
indicator on the CP1W-CIF11 is flashing.
6-4-4 E5@C-T Controller Setup

Table of Contents

Other manuals for Omron E5*C Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5*C Series and is the answer not in the manual?

Omron E5*C Series Specifications

General IconGeneral
BrandOmron
ModelE5*C Series
CategoryController
LanguageEnglish

Related product manuals