7 Component Communications
7 - 4
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
This section describes the settings necessary to start component communications and the set point
calculations that are used to perform target point calculations at the slaves.
To perform component communications, change the parameter settings in the communications setting
level to the values that are given below.
* Parameter details are the same as for programless communications. Refer to 6-2 E5
@
C-T Controller Setup.
Note: To use component communications, the input type and, if an analog input is used, the decimal point position
must be set to the same values for all of the E5@C-T/E5@C Controllers. The operation will not work correctly
if the position of the decimal point is different.
The parameters that are used for component communications are shown with a gray background in the
following diagram. All of these parameters are displayed if you set the Protocol Setting parameter to
cmp. (Some of the parameters are always displayed.)
* These parameters are displayed regardless of the setting of the Protocol Setting parameter.
Note: The Communications Data Length, Communications Stop Bits, and Communications Parity parameters in
the communications setting level are not displayed.
7-1-3 E5@C-T Controller Setup
Parameter
Set value
Master (E5@C-T) Slaves (E5@C)
Protocol setting CMP CMP
Communications unit
number
0 A number is set for each slave in order
from 1.
Communications baud rate 57.6 (recommended) 57.6 (recommended)
Send data wait time 1 (recommended) 1 (recommended)
Highest communications
unit No.
Highest communications unit number of
all the slaves
Setting is not necessary
(The parameter is not displayed.)
M
M
M
M
M
Communications unit No. = 0 (master) Communications unit number 0
(slave (Fixed-value Controller)
M
M
M
M
M
M
25
0
psel
cmp
u-no
0
bps
57.6
sdwt
20
maxu
0
sps
1.000
spos
0.0
rwat
1000
l.adj
1234
at
off
cmwt
on
in-t
5
Initial Setting Level
Operation Level
Protocol Setting
*
Communications
Unit No.
*
Communications
Baud Rate
*
Send Data Wait
Time
*
Highest
Communications
Unit No.
Receive Data
Wait Time
Communications Setting Level
Power ON
SP Slope
SP Offset
Adjustment Level
Display
AT Execute/Cancel
Communications
Writing
*
Adjustment Level
Press
O
Key
for less than 1 s.
Press
O
Key
for less than 1 s.
Press
O
Key
for at least 3 s.
Press
O
Key
for at least 1 s.

Table of Contents

Other manuals for Omron E5*C Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5*C Series and is the answer not in the manual?

Omron E5*C Series Specifications

General IconGeneral
BrandOmron
ModelE5*C Series
CategoryController
LanguageEnglish

Related product manuals