Overview
1.1 Overview of Communications Methods
1-9
• Communications Stop Bits (sbit)
This parameter is for setting the number of communications stop bits.
Set either “1” or “2.”
• Communications Parity (prty)
The communications parity can be set. Set the parity to “none,” “even,”
or “odd.”
• Send Data Wait Time (sdwt)
The send data wait time is the delay from when the Controller receives
a command from the host computer until it returns a response. If the
response is returned too quickly, the host computer may not be able to
receive the response. Change the send data wait time as required. To
increase the response speed for communications, reduce the send data
wait time. The send data wait time can be set in 1-ms increments
between 0 and 99 ms. The default is 20 ms.
● Setting Communications Writing
Set the communications writing parameter to ON to allow the host to
write to the E5CN/AN/EN/GN via communications.
Parameter Setting
1. Press the O Key for less than one second to move from the operation
level to the adjustment level.
2. Select the parameter as shown below by pressing the M Key.
3. Press the U or D Key to set the communications writing parameter
to ON.
c
l.adj
c
at
off
c
cmwt
off
c
cmwt
on
Adjustment Level
Display
Displayed only once when
entering adjustment level.
AT Execute/Cancel
Communications
Writing
•
•
•
•