E5@C Digital Temperature Controllers User’s Manual (H174)
A-6 Parameter Operation Lists
A
A-6-6 Advanced Function Setting Level
Display Brightness brgt 1 to 3 3 None
Alarm 1 Latch a1lt OFF, ON off, on OFF None
Alarm 2 Latch a2lt OFF, ON off, on OFF None
Alarm 3 Latch a3lt OFF, ON off, on OFF None
Alarm 4 Latch a4lt OFF, ON off, on OFF None
Move to Protect Level
Time
prlt 1 to 30 3 Second
Cold Junction
Compensation Method
cjc OFF, ON off, on ON None
Alarm 1 ON Delay a1on 0 to 999 (0: ON delay disabled) 0 Second
Alarm 2 ON Delay a2on 0 to 999 (0: ON delay disabled) 0 Second
Alarm 3 ON Delay a3on 0 to 999 (0: ON delay disabled) 0 Second
Alarm 4 ON Delay a4on 0 to 999 (0: ON delay disabled) 0 Second
Alarm 1 OFF Delay a1of 0 to 999 (0: OFF delay disabled) 0 Second
Alarm 2 OFF Delay a2of 0 to 999 (0: OFF delay disabled) 0 Second
Alarm 3 OFF Delay a3of 0 to 999 (0: OFF delay disabled) 0 Second
Alarm 4 OFF Delay a4of 0 to 999 (0: OFF delay disabled) 0 Second
MV at Stop and Error
Addition
mvse OFF, ON off, on OFF None
Auto/Manual Select
Addition
amad OFF, ON off, on Standard
Model:OFF
Position-pro
portional
Model: ON
None
Manual Output Method mant HOLD or INIT hold, init HOLD None
Manual MV Initial Value mani
−5.0 to 105.0 for standard control
*1
−105.0 to 105.0 for heating/cooling control
*1
0.0 %
RT
rt OFF, ON off, on OFF None
HS Alarm Use hsu OFF, ON off, on ON None
HS Alarm Latch hsl OFF, ON off, on OFF None
HS Alarm Hysteresis hsh 0.1 to 50.0 0.1 A
LBA Detection Time lba 0 to 9999 (0: LBA function disabled) 0 Second
LBA Level lbal Temperature input: 0.1 to 999.9 8.0 °C or °F
Analog input: 0.01 to 99.99 10.00 %FS
LBA Band lbab Temperature input: 0.0 to 999.9 3.0 °C or °F
Analog input: 0.00 to 99.99 0.20 %FS
Parameters Characters Setting (monitor) value Display Default Unit