Conformance to UL and CSA Standards
Some NX-series products comply with UL and CSA standards.
If you use a product that complies with UL or CSA standards and must apply those standards to your
machinery or devices, refer to the Instruction Sheet that is provided with the product. The Instruction
Sheet provides the application conditions for complying with the standards.
Conformance to KC Certification
When you use this product in South Korea, observe the following precautions.
This product meets the electromagnetic compatibility requirements for business use. There is a risk of
radio interference when this product is used in home.
Usage Conditions for KC Certification
Take the same measures as those described in Conformance to EU Directives on page 35
. In addi-
tion, attach a clamp core to the port side of the EtherNet/IP cable.
The recommended clamp core is given below
.
Recommended Clamp Core
Manufacturer Product Model Turns of cable
NEC TOKIN Clamp core ESD-SR-250 1 turn
Conformance to Shipbuilding Standards
This product complies with the following shipbuilding standards. Applicability to the shipbuilding stand-
ards is based on certain usage conditions. It may not be possible to use the product in some locations.
Contact your OMRON representative before attempting to use a Controller on a ship.
Usage Conditions for NK and LR Shipbuilding Standards
• This product must be installed within a control panel.
• Gaps in the door to the control panel must be completely filled or covered with gaskets or other ma-
terial.
•
The following noise filter must be connected to the power supply line.
Noise Filter
Manufacturer Model
Cosel Co., Ltd. TAH-06-683
Regulations and Standards
36
NX-series NX1P2 CPU Unit Hardware User’s Manual (W578)