6-17
n48 Number of Fault Retries Changes during
operation
No
Setting
range
0 to 10 Unit of
setting
1 Default setting 0
Set Values
•Set the number of fault retries required.
•The count of fault retries will be cleared in any of the following cases.
The Inverter is normal for 10 minutes continuously after the latest fault retry was
made.
Power supply to the Inverter is interrupted.
A fault reset is input.
6-7-5 Frequency Jump Function (n49 to n51)
•The frequency jump function prevents the Inverter from generating frequencies that
make the mechanical system resonate.
•The frequency jump function can be used effectively to set two dead bands of a fre-
quency reference.
n49 Jump Frequency 1 Changes during
operation
No
Setting
range
0.0 to 400 (Hz) Unit of
setting
0.1 Hz
(see note)
Default setting 0.0
n50 Jump Frequency 2 Changes during
operation
No
Setting
range
0.0 to 400 (Hz) Setting
range
0.1 Hz
(see note)
Unit of setting 0.0
n51 Default Setting Changes during
operation
No
Setting
range
0.0 to 25.5 (Hz) Unit of
setting
0.1 Hz Default setting 0.0
Note Values
will be
set in 0.1-Hz increments if the frequency is less than 100 Hz and
1-Hz increments if the frequency is 100 Hz or greater.
Advanced Operation Chapter
6