5-8 Selecting the Interruption Mode
This parameter is used to specify the interruption mode when the STOP
command is input.
The
Inverter either decelerates or coasts
to a stop according to the inter
-
ruption mode selection.
H Selecting the Interruption Mode (n04)
n04 Interruption Mode Selection Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 Frequency deceleration stop (see note)
1 Free running
Note The
Inverter will decelerate to stop according to the setting in n17 for deceleration
time
1 if any of the n36 through
n39 parameters for multi-function input is not set to
11
for acceleration/deceleration time selection. If any one of the n36 through n39
multi-function
input parameters is
set to acceleration/deceleration time selection,
the
Inverter will decelerate to stop according to the selected setting of decelera
-
tion time when the STOP command is input.
Basic Operation Chapter