102
IP Addresses in FINS Communications Section 5-2
2. Set IP addresses for the devices to be connected.
Set the IP address for the remote EtherNet/IP Unit or built-in EtherNet/IP
port (i.e., the server) connected by FINS/TCP.
This setting must be made if this EtherNet/IP Unit will be used as a FINS/
TCP client.
5-2-3 Application Examples
Responding to Computers with Changed IP Addresses
FINS/UDP
Communications Method
With FINS/UDP, whether using the automatic conversion method (dynamic),
the IP address table method, or the combined method, remote FINS node
addresses and remote IP addresses in the internal table are changed after
FINS messages are received. Therefore, even when a FINS command has
been received from a personal computer (a DHCP client computer) for which
the IP address is dynamically changed, a response can still be sent back to
the computer (the DHCP client computer) from which the command origi-
nated.
FINS/TCP
Communications Method
With FINS/TCP, FINS node addresses and IP addresses in the internal table
are changed with each connection that is established. Therefore, even when a
FINS command has been received from a personal computer (a DHCP client
computer) for which the IP address is dynamically changed, a response can
still be sent back to the computer (the DHCP client computer) from which the
command originated.
Note Automatic IP Address Setting by DHCP Service
DHCP service is a method whereby a DHCP server collectively manages all
of the IP address in a network.
Nodes that are functioning as clients acquire IP addresses from the DHCP
Personal computer (client)
IP address changed
(acquired from DHCP server when connected)
FINS command sent
IP address
IP address
FINS command
FINS response
Ethernet (EtherNet/IP)
Response sent back to
changed IP address
EtherNet/IP Unit
(with fixed IP address)
Personal computer (client)
IP address changed
(acquired from DHCP server when connected)
FINS command sent
IP address
IP address
FINS command
FINS response
Response sent back to
changed IP address
EtherNet/IP Unit
(FINS/TCP server; with
fixed IP address)
Ethernet (EtherNet/IP)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CJ1W-EIP21 and is the answer not in the manual?

Omron SYSMAC CJ1W-EIP21 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CJ1W-EIP21
CategoryNetwork Hardware
LanguageEnglish

Related product manuals