397
FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E
Response Codes
BROADCAST TEST RESULTS READ
Reads the results (number of times data received) of the broadcast test.
Command Block
Response Block
Parameters
Times Received (Response)
The number of times the data has been received normally during the broadcast send test is returned as a
hexadecimal number. The number of times received is cleared each time the result is read.
Response Codes
BROADCAST DATA SEND
Sends test data simultaneously to all nodes on the network.
Command Block
Parameters
Test Data (Command)
This command specifies the data to be sent to the specified nodes. Up to 1,460 bytes can be specified.
Response code Description
0000 Normal end
1001 Command too large
1002 Command too small (No test data)
08 02
Command
code
08 02
Times
received
Response
code
Command
code
Response code Description
0000 Normal end
1001 Command too large
08 03
Command
code
1,460 bytes max.
Test data

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CJ1W-EIP21 and is the answer not in the manual?

Omron SYSMAC CJ1W-EIP21 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CJ1W-EIP21
CategoryNetwork Hardware
LanguageEnglish

Related product manuals