Using the LED Indicators and Display for Troubleshooting Section 14-2
Ethernet Information Tab
Page
The Ethernet Information Tab Page shows the communications status at the
communications driver level. The error counter information can be used to
confirm whether communications problems have occurred. The tag data link
information can be used to confirm characteristics such as the bandwidth
usage (pps).
14-2 Using the LED Indicators and Display for Troubleshooting
14-2-1 Errors Occurring at the EtherNet/IP Unit or Built-in EtherNet/IP
Port
Errors Related to CPU Unit
Data Exchange
The 7-segment display alternates between the node address and error code.
Indicator Error Cause Unit operation (Flag
status)
Error
log
(hex)
Countermeasure
MS NS 7-segment
Flashing
red
Not lit H1 Duplicate unit
number
The same unit
number is set on
another Unit.
Operation stops. --- Set the unit num-
bers correctly and
restart the Ether-
Net/IP Unit or built-
in EtherNet/IP port.
Flashing
red
Not lit H2 CPU Unit
faulty
--- Operation stops. --- Replace the CPU
Unit if the error
recurs when the
CPU Unit is
restarted.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CJ1W-EIP21 and is the answer not in the manual?

Omron SYSMAC CJ1W-EIP21 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CJ1W-EIP21
CategoryNetwork Hardware
LanguageEnglish

Related product manuals