COMMUNICATION PORTS
The following communication ports are present on the upper part of the UPS behind the door (see UPS Views):
Serial port, available with RS232 and USB connectors.
NOTE: use of one connector automatically excludes the other
Expansion slot for additional COMMUNICATION SLOT communication boards
AS400 Port
It is also possible to install an optional MultiCOM 382 contact board (4 programmable contacts, 250V AC, 3A) on the rear of the
UPS
RS232 AND USB CONNECTORS
RS232 CONNECTOR
USB CONNECTOR
PIN # NAME TYPE SIGNALS PIN # SIGNALS
1 IN 1 VBUS
2 TX OUT TX serial line 2 D-
3 RX IN RX serial line 3 D+
4 4 GND
5 GND POWER
6 OUT
7
8 +15V POWER
Isolated power
15V±5% 80mA max
9 WKATX OUT ATX power adapter activator
COMMUNICATION SLOT
The UPS is supplied with two expansion slots for optional communication cards that allow the device to communicate using the
main communication standards (see "User interface").
Some examples:
Second RS232 port
Serial duplicator
Ethernet network card with TCP/IP, HTTP and SNMP
protocols
RS232 + RS485 ports with JBUS / MODBUS protocol
Refer to the website for further information regarding available accessories
12
34

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Riello UPS Multi Sentry 160 MST and is the answer not in the manual?

Riello UPS Multi Sentry 160 MST Specifications

General IconGeneral
BrandRiello UPS
ModelMulti Sentry 160 MST
CategoryUPS
LanguageEnglish

Related product manuals