HVLS Fan Installation/Service/Owner's Manual Rite‑Hite
®
ELECTRICAL
EMC Compliance (OPTIONAL)
The EMC Compliance Option includes an EMC lter on
the line side of the VFD.
To maintain IEC 61800‑3 C1 compliance, you must
observe the following installation guidelines:
Ensure maximum physical separation between low
voltage control cables and high voltage power cables
(minimum 150mm or 6in).
Ensure maximum physical separation between motor
cable and all other circuits (minimum 150mm or 6in).
Use shielded, low capacitance VFD cable with XLPE
(Cross‑linked Polyethylene) insulation. Example
products:
Belden 29501
AlphaWire V16014
Ground the motor cable shield at both ends of the
cable (VFD and motor).
The total motor cable length must not exceed exceed
65ft [20m].