Troubleshooting
Samsung Electronics 4-3
غ
Commissioning
ـ After initial installation, stable operation for a certain period of time limited to operation conditions.
Cooling Heating
Method of EntryK2 Tact Switch twice K2 Tact Switch twice
Compressor Normal operation, but the maximum fr equency limit (diff er by model)
Indoor Unit Whole operation (The set t emperature=3πC) Whole operation (The set t emperature=40πC)
Outdoor
fan and valves Normally control conduct
Operation time Min : 60 minutes, Max : 10 hours
Etc.  Exceed the maximum operating time at st ops and waits .
Prot ection and control, self-diag nosis is performed.
غ
Refrigerant lling operation
ـ Operation to filling the refrigerant compressor was fixed at a certain frequency.
Cooling Heating
Method of EntryK2 Tact Switch one time K1 Tact Switch one time
Compressor Starting frequency (Mild Start frequency) operation
Indoor Unit Whole operation (The set temperature=3πC) Whole operation (The set temperature=40πC)
Outdoor fan and valv
es Normally control conduct
Operation time 60 minutes
Etc. During the filling operation does not enter the special operation, such as oil recovery, defrost.

Table of Contents

Other manuals for Samsung AM160FNBFEB/EU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AM160FNBFEB/EU and is the answer not in the manual?

Samsung AM160FNBFEB/EU Specifications

General IconGeneral
TypeAir conditioner indoor unit
Multi-split-
Product colorWhite
Gas hose diameter15.88 mm
Liquid hose diameter9.52 mm
Refrigerating mediumR410A
Air conditioner functionsHeating
Heating capacity (nominal)54600 BTU/h
Heating capacity in watts (max)16000 W
Cooling capacity in watts (nominal)- W
Operating temperature (heating) (T-T)-20 - 24 °C
AC input voltage220-240 V
Current (heating)14.3 A
AC input frequency50-60 Hz
Design load (cooling)- kW
Energy efficiency scaleA++ to G
Power consumption (heating) (max)3100 W
Hourly energy consumption (cooling)- kWh
Energy efficiency class (heating) (Average heating season)A++
Indoor unit typeWall-mountable
Indoor unit depth330 mm
Indoor unit width518 mm
Indoor unit height1210 mm
Indoor unit weight104000 g
Indoor units quantity1
Indoor unit package depth426 mm
Indoor unit package width652 mm
Indoor unit package height1289 mm
Indoor unit package weight107000 g
Indoor unit sound power level42 dB
Indoor unit noise level (high speed)60 dB
Outdoor unit noise level- dB

Related product manuals